Specifications
Specifications | ||
Jaw opening | 12.9 mm (0.5 in) | |
Max wire size | 1/0 THHN Cable | |
Current range AC rms | 0 to 100.0 A | |
Accuracy AC current (50/60 Hz) | 3% ± 3 counts | |
AC response | Averaging | |
Voltage range AC/DC | 0 to 600 V | |
Voltage accuracy | AC | 1.5% ± 2 counts |
DC | 1% ± 1 count | |
Resistance range | 0 to 1000 Ω | |
Continuity beeper threshold | On at < 25 Ω, off at > 400 Ω | |
Volts indicator LED threshold | Guaranteed on by 30 V AC | |
Environmental Specifications | ||
Operating temperature | -10°C to 50°C | |
Storage temperature | -30°C to 60°C | |
Humidity (without condensation) | 0% to 95% (5°C to 30°C); 0% to 75% (30°C to 40°C); 0% to 45% (40°C to 50°C) | |
Dust/water resistance | Yes | |
Operating altitude | 2000 meters max | |
Temperature coefficient | 0.1 x (specified accuracy)/°C (< 18°C or > 28°C) | |
Safety Specifications | ||
Measurement Category | IEC 61010-2-032, IEC61010-2-033: CAT III 600 V, 100 A ac | |
Agency approvals | CSA, TUV | |
Maximum voltage | 600 V between any terminal and earth ground | |
Mechanical and General Specifications | ||
Size | 30.5 x 51 x 203 mm | |
Weight | 300 g | |
Warranty | Two-years | |
Battery life | 200 hour zinc chloride, 400 hour alkaline | |
Battery type | 2 x AA | |
Low battery indicator | Yes | |
Current sensor opening | 12.9 mm |